UPS Prolink 10KVA PRO-810QRS Rackmount Online 12V9AH x 20units
-Capacity: 10kVA / 10KW ; Input frequency range [40 – 70 Hz] ;
-Input power factor ≥ 0.99 @ Nominal Voltage (100% load)
– Ouput power factor = 90% – 100%
-Hot-swappable battery design ; Smart battery charger
-Parallel function
-Output Voltage 208*/220/230/240 VAC
-Noise Level: Less than 58dB @ 1 Meter
-Input Power Voltage : 110 – 300 VAC
-Back-Up Time Half Load: 9.5 minutes
-Back-Up Time Full Load: 3 minutes
-Dimension: 75,4 x 48,2 x 14,6 cm
-Weight: 99 Kg
GENERAL
UPS Type Rack / Tower
Phase 1 phase in / 1 phase out
Rating (VA) 10000
Nominal Power (W) 10000
Standard Model Dimension (mm) UPS Unit: 610 x 438 x 88 [2U] (D x W x H) Battery Pack: 600 x 438 x 133 [3U] (D x W x H)
Weight (kg) UPS Unit: 20 Battery Pack: 63
Long-run Model Dimension (mm) 610 x 438 x 88 [2U] (D x W x H)
Weight (kg) 20
INPUT
Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC VAC
Voltage Range 110~300VAC ± 3% at 50% load 176~300VAC ± 3% at 100% load
Frequency Range 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
Power Factor ≧0.99
THDi < 4% @100% Load < 6% @50% Load
OUTPUT
Connection Type Terminal
Nominal Voltage 208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦1% THD (Linear load) ≦4% THD (Non-linear load)
ALARM & INDICATORS
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault
CONNECTIVITY, CONTROL & MONITORING
Front panel Status LED, Function keys, LCD display
Communication Smart RS232* USB Port Emergency Power Off (EPO)
BATTERY
Standard Model Type 12V / 9Ah
Numbers 20
Typical Recharge Time 9 hours recover to 90% capacity
Long-run Model Type Depending on the capacity of external batteries
Numbers 16 – 20 **
Charging Current (max) 4.0 A
REAR PANEL
1.Share current port (only available for parallel model)
2.Parallel port (only available for parallel model)
3.External battery connector
4.Intelligent slot
5.RS-232 communication port
6.USB communication port
7.Emergency power off function connector (EPO connector)
8.Input circuit breaker
9.Output terminals
10.Ground
11.Input terminals
12.Cooling Fan
13.External maintenance bypass switch port
Tags: UPS, Prolink, Online, 10KA, Rackmount