Capacity
PRO901-ERS 1KVA: 1000VA / 900W
PRO902-ERS 2KVA: 2000VA / 1800W
PRO903-ERS 3KVA: 3000VA / 2700W
PRO906-ERS 6KVA: 6000VA / 5400W
PRO910-ERS 10KVA: 10000VA / 9000W
UPS type
Tower
Input phase
Single phase with ground
Input nominal voltage
For 1000VA, 2000VA, and 3000VA: 200/208/220/230/240VAC
For 6000VA and 10000VA: 208/220/230/240VAC
Input voltage range
For 1000VA, 2000VA, and 3000VA:
110-300VAC (Based on load at 50%)
160-280VAC (Based on load at 100%)
For 6000VA and 10000VA:
110-300VAC (Based on load at 50%)
176-300VAC (Based on load at 100%)
Input frequency
For 1000VA, 2000VA, and 3000VA:
40 - 70Hz
For 6000VA and 10000VA:
46-54Hz or 56-64Hz
Input power factor
≧ 0.99 @ nominal voltage (100% load)
Output voltage regulation
±1%
Output frequency
For 1000VA, 2000VA, and 3000VA:
Synchronized range: 47 - 53Hz or 57 - 63Hz
Battery mode: 50Hz ± 0.25Hz or 60Hz ± 0.3Hz
For 6000VA and 10000VA:
Synchronized range: 46 - 54Hz or 56 - 64Hz
Battery mode: 50Hz or 60Hz ± 0.1Hz
Output current crest ratio
3:1
Output harmonic distortion
For 1000VA, 2000VA, and 3000VA:
≦ 3% THD (Linear load)
≦ 6% THD (Non-linear load)
For 6000VA and 10000VA:
≦ 3% THD (Linear load)
≦ 5% THD (Non-linear load)
Battery type and number
1000VA - 12V/9Ah x 2pcs
2000VA - 12V/9Ah x 4pcs
3000VA - 12V/9Ah x 6pcs
6000VA & 10000VA - 12V/9Ah x 16pcs
Battery recharge time
1000VA, 2000VA, and 3000VA - 4 hours to 90% capacity
6000VA and 10000VA - 9 hours to 90% capacity
Alarm
Battery mode - Sounding every 4 seconds
Low battery - Sounding every second
Overload - Sounding twice every second
Faulty - Continuously sounding
LCD indicators
Load level, battery level, AC mode, battery mode, bypass mode, and fault indicators
Front panel
Status LED, function keys, LCD display
Communication
Smart RS232 and USB port
Tags: UPS, Prolink, Online, 1KVa
Home Banner Full Width 1 (CMS)